Limiting electric strength of vacuum electrode systems including combined breakdown
Tóm tắt
There exists three types of emission sites, eventually being a place of initiation of electric breakdown in vacuum switching devices with a screened insulator. Using electrostatic field calculations, potential breakdown paths, which start at the emission site in a vacuum interrupter, have been analyzed. Combined breakdown includes a breakdown path across two vacuum gaps and formation of flashover along an insulator. The paper discusses physical models of electron current multiplication at the insulator surface leading to the breakdown initiation.
Từ khóa
#Vacuum breakdown #Vacuum systems #Electrodes #Electric breakdown #Breakdown voltage #Dielectrics and electrical insulation #Interrupters #Testing #Electrostatics #FlashoverTài liệu tham khảo
10.1063/1.327839
ryl'skaya, 2001, Electrotekhnika N 03/01, 7
banaszak, 1990, Proc 14 ISDEIV Santa-Fe, 357
chalmers, 1996, Proc 17 ISDEIV Berkeley, 1, 420
nevmysky, 1998, Proc 18 ISDEIV Eindhoven, 159
10.1109/TEI.1985.348907
finke, 1966, Proc Second Intern Symp on Insul of High Voltages in Vacuum USA, 217