Peculiarities of nonsustained disruptive discharges at interruption of cable/line charging current

A.M. Chaly1, L.V. Denisov1, V.N. Poluyanov1, I.N. Poluyanova1
1Tavrida Electric, Sevastopol, Ukraine

Tóm tắt

It has been found out that NSDD probability increases at cable/line charging current interruption compared with no-load test. This fact has been explained by formation of contact welds at closing of the preliminary charged cable/line. These welds being torn apart at the following contact partition may serve as a source of macroparticles or surface irregularities resulting in increased probability of NSDD.

Từ khóa

#Circuit testing #Electric breakdown #Voltage #Probability #Contacts #Surges #Hafnium #Surface charging #Surface discharges #Fault location

Tài liệu tham khảo

schlaug, 1988, Proc XIXth ISDEIV, 267 juttner, 1999, J Phys D Appl Phys, 32 slade, 1999, Electrical Contacts, 513, 10.1201/9780585139319 10.1109/14.231527 juttner, 1999, J Phys D Appl Phys, 32 rylskaya, 1988, Proc XXIth ISDEIV, 267