Experimental analysis of ion parameters during the forced vacuum arc interruption

A. Klajn1
1Institute of Electrical Power Engineering, Wroclaw University of Technology, Wroclaw, Poland

Tóm tắt

The paper presents experimental measuring results of the ion decay time during the post-arc phase after a forced interruption of diffuse vacuum arc. Arc current of amplitudes 400 A and 600 A was switched-off using counter-pulse current with falling rates from 2 A//spl mu/s u to 67 A//spl mu/s in a laboratory test circuit. The used voltage, current and contact parameters were representative for a low-voltage vacuum switch. The decay process of ion current was observed, using a retarding field analyser. First, a series of introductory measurements concerning probe calibration were performed. The decay times of ions were measured as function of the falling rate of the counter-current, and mean values from about 60 /spl mu/s at arc current falling rate 2 A//spl mu/s up to 35 /spl mu/s at arc current falling rate 67 A//spl mu/s were measured. Only a small dependence of the decay time from the arc current value (400 A or 600 A) was observed. The decay time decreases significantly with increasing of the counter-current failing rate. The results are proposed as a parameter in the modelling of post-arc phenomena of low voltage vacuum switches.

Từ khóa

#Vacuum arcs #Circuit testing #Switches #Current measurement #Force measurement #Phase measurement #Time measurement #Switching circuits #Laboratories #Voltage

Tài liệu tham khảo

10.1109/27.21671 10.1109/TPS.1983.4316248 lindmayer, 1993, AKlajn VII International Conf Switcting Are-Phenomena, 83 10.1109/27.782261 pitts, 1990 dunning, 2000, XIXth Int Symposium on Discharges and Electrical lnsulation in Vacuum Xi'an childs, 1980, IEEE Trans on PlasmaScience -PS-8, 289 10.1063/1.1693433