Breaking performance of a capacitive-graded series design of two 24-kV vacuum circuit breakers
Tóm tắt
This contribution deals with the breaking capability of a series design consisting of two 24-kV vacuum circuit breakers (VCB) with grading capacitors. In previous publications it was shown that the breaking capability of the series arrangement is higher compared to the double of a single tube. In addition to these results it is shown that in some cases grading capacitors can increase the breaking capacity even more. Tests with simultaneous opening of the contacts of both tubes are presented with the application of different grading capacitors as well as the choice of different arcing times. In case of reignition of one of the tubes the current circulating between the two tubes is shown. As a result of the tests the breaking capability of the arrangement depending on the arcing time and the value of the grading capacitors can be classified into three zones: area of reignition of the arrangement, scatter area and area of successful arc quenching.
Từ khóa
#Circuit breakers #Voltage #Circuit testing #Capacitors #Vacuum systems #Transient analysis #Electromagnetic measurements #Vacuum technology #Vacuum arcs #ActuatorsTài liệu tham khảo
10.1109/94.993729
0, Information SIEMENS AG, Traction Power Supply from Siemens, Single Pole Vacuum Interrupter Department Traction Power Supply (E 43) Erlangen Germany (in German)
betz, 1999, Breaking Performance of Vacuum Tubes Connected in Series Considering the Distribution of Electric Potential (In German)
fink, 1984, SF6-insulated medium-voltage switchgear with vacuum circuit-breakers (in German) etz, 115, 622
biewendt, 1993, Influence of shield- and contact-geometry on the are quenching capability of vacuum circuit breakers (in German)