3D finite element simulation and synthetic tests of vacuum interrupters with axial magnetic field contacts
Tóm tắt
Axial magnetic field improves the interruption ability of vacuum circuit breakers. It is known that the design influences the axial magnetic field (AMF) distribution, current distribution and hence the interruption performance. In this paper, the authors present a numerical and experimental study for several segmented coil geometries. The numerical study involves three-dimensional AMF simulations and the? experimental study evaluates their performance in short-circuit interruption tests. The calculations are analysed for magnetic field distribution. Two empirical models, which relate to the performance design parameters are widely accepted. From this, they deduce several criteria for "effective contact area" depending on the magnetic field strength and position (in time and in space). The first results suggest that the interruption ability of AMF vacuum interrupters could be described by a simple relationship. the interruption ability is proportional to the square of the contact diameter times the "effective area" percentage.
Từ khóa
#Finite element methods #Interrupters #Magnetic fields #Circuit simulation #Circuit testing #Circuit breakers #Current distribution #Coils #Geometry #Magnetic analysisTài liệu tham khảo
matsui, 2000, Proc 19th ISDEIV, 447
10.1109/61.634170
0, High-voltage test techniques, IEC 60060–1 (1989–11), 91
fenski, 2000, Proc 19th ISDEIV, 451
stoving, 1998, Proc 18th ISDEIV, 522
yanabu, 1986, Proc 12th ISDEIV, 186
fink, 2000, Proc 19th ISDEIV, 375
fenski, 1998, Proc of 18thISDEIV, 459
10.1109/95.296368
fenski, 1996, Proc 17thISDEIV, 337