Use of personalized ventilation for improving health, comfort, and performance at high room temperature and humidity

Indoor Air - Tập 23 Số 3 - Trang 250-263 - 2013
Arsen Krikor Melikov1,2,3,4,5,6,7,8,9,10, M. Skwarczyński11,7, Jan Kaczmarczyk12, J. Zabecky7
1A. K. Melikov
2Building 402, 2800 Kgs. Lyngby
3Denmark
4Department of Civil Engineering
5Fax: +45 45932166
6International Centre for Indoor Environment and Energy
7International Centre for Indoor Environment and Energy, Department of Civil Engineering, Technical University of Denmark, Kgs. Lyngby, Denmark
8Nils Koppels Alle
9Technical University of Denmark
10Tel.: +45 45254013
11Faculty of Environmental Engineering, Institute of Environmental Protection Engineering, Department of Indoor Environment Engineering, Lublin University of Technology, Lublin, Poland
12Faculty of Energy and Environmental Engineering, Department of Heating, Ventilation and Dust Removal Technology, Silesian University of Technology, Gliwice, Poland

Tóm tắt

Từ khóa


Tài liệu tham khảo

Andersson, 2007, Indoor climate and productivity in offices. How to integrate productivity in life-cycle cost analysis of building services

ASHRAE, 2010, Thermal environmental conditions for human occupancy

ASHRAE Guideline 10, 2011, Interactions affecting the achievement of acceptable indoor environments

Bauman, 1998, Field study of the impact of a desktop task/ambient conditioning system in office buildings, ASHRAE Trans., 104, 1153

Bedford, 1966, Basic principles of ventilation and heating

Berglund , B. Cain , W.S. 1989 Perceived air quality and the thermal environment 93 99

Bolashikov, 2003, New air terminal devices with high efficiency for personalized ventilation application, Proc. Healthy Build., 2, 850

Cermak, 2007, Protection of occupants from exhaled infectious agents and floor material emissions in rooms with personalized and underfloor ventilation, HVAC & R Res., 13, 23, 10.1080/10789669.2007.10390942

Cermak, 2006, Performance of personalized ventilation in conjunction with mixing and displacement ventilation, HVAC & R, 12, 295, 10.1080/10789669.2006.10391180

EN 15251, 2007, Criteria for indoor environment including thermal, indoor air quality, light and noise

Halvoňová, 2010, Performance of “ductless” personalized ventilation in conjunction with displacement ventilation: Impact of disturbances due to walking person(s), Build. Environ., 45, 427, 10.1016/j.buildenv.2009.06.023

Hart , S.G. 2006 NASA-Task Load Index (NASA-TLX); 20 years later 904 908

Horwath, 2001, Ocular Ferning test - effect of temperature and humidity on tear Ferning patterns, Ophthalmologica, 215, 102, 10.1159/000050838

ISO 7730, 2005, Moderate thermal environment - determination of the PMV and PPD indices and specification of the conditions for thermal comfort

Kaczmarczyk, 2004, Human response to personalized and mixing ventilation, Indoor Air., 14, 1, 10.1111/j.1600-0668.2004.00300.x

Kaczmarczyk, 2006, Human response to five designs of personalized ventilation, HVAC & R Res., 12, 367, 10.1080/10789669.2006.10391184

Krogstad, 1991, A prospective study of indoor climate problems at different temperatures in offices (in Swedish)

Lan, 2011, Effects of thermal discomfort in an office on the perceived air quality. Sick Building Syndrome-symptoms, physiological responses and human performance, Indoor Air., 21, 376, 10.1111/j.1600-0668.2011.00714.x

Li, 2010, Thermal comfort and IAQ assessment of under-floor air distribution system integrated with personalized ventilation in hot and humid climate, Build. Environ., 45, 1906, 10.1016/j.buildenv.2010.03.003

Melikov, 2004, Personalized ventilation, Indoor Air., 14, 157, 10.1111/j.1600-0668.2004.00284.x

Melikov, 2012, Air movement and perceived air quality, Build. Environ., 47, 400, 10.1016/j.buildenv.2011.06.017

Melikov , A. Kaczmarczyk , J. Sliva , D. 2008 Impact of air movement on perceived air quality at different level of relative humidity

Melikov , A.K. Lyubenova , V.S. Skwarczynski , M. Kaczmarczyk , J. 2011 Impact of air temperature, relative humidity, air movement and pollution on eye blinking

Rolando, 1984, Tear mucus ferning test in normal and keratoconjunctivitis sicca eyes, Chibret Int. J. Ophthalomol., 2, 32

Schiavon, 2008, Energy saving and improved comfort by increasing air movement, Energy Build., 40, 1954, 10.1016/j.enbuild.2008.05.001

Schiavon, 2009, Energy-saving strategies with personalized ventilation in cold climates, Energy Build., 41, 543, 10.1016/j.enbuild.2008.11.018

Schiavon, 2010, Energy analysis of the personalized ventilation system in hot and humid climates, Energy Build., 42, 699, 10.1016/j.enbuild.2009.11.009

Sekhar, 2005, Findings of personalized ventilation studies in a hot and humid climate, HVAC & R Res., 11, 603, 10.1080/10789669.2005.10391157

Sekhar , C. Li , R. Melikov , A.K. 2010 Use of heat-pipe for energy efficiency improvement of personalized ventilation system combined with under-floor air distribution system in a hot and humid climate

Skwarczynski, 2010, Impact of individually controlled facially applied air movement on perceived air quality at high humidity, Build. Environ., 45, 2170, 10.1016/j.buildenv.2010.03.017

Sundell, 2011, Ventilation rates and health: multidisciplinary review of the scientific literature, Indoor Air, 21, 191, 10.1111/j.1600-0668.2010.00703.x

Tham, 2009, Room air temperature affects occupants' physiology, perceptions and mental alertness, Build. Environ., 45, 40, 10.1016/j.buildenv.2009.04.002

Tsutsumi , H. Hoda , Y. Tanabe , S. Arishiro , A. 2007 Subjective eye comfort and performance under the different combination of humidity, local air velocity and illuminance

Wolkoff, 2008, “Healthy” eye in office-like environments, Environ. Int., 34, 1204, 10.1016/j.envint.2008.04.005

Wyon, 2009, Measurement of acute response to draught in the eye, Acta Ophthalmol., 65, 385, 10.1111/j.1755-3768.1987.tb07011.x

Yang, 2009, Performance evaluation of ceiling mounted personalized ventilation system, ASHRAE Trans., 115, 395

Yang, 2010, Ceiling mounted personalized ventilation system integrated with a secondary air distribution system - a human response study in hot and humid climate, Indoor Air, 20, 309, 10.1111/j.1600-0668.2010.00655.x

Zhang, 2010, Comfort, perceived air quality, and work performance in a low-power task-ambient conditioning system, Build. Environ., 45, 29, 10.1016/j.buildenv.2009.02.016