Natural convection liquid desiccant loop as an auxiliary air conditioning system: investigating the operational parameters

Heat and Mass Transfer - Tập 54 - Trang 903-913 - 2017
Mohammad Ali Fazilati1, Ali Akbar Alemrajabi2, Ahmad Sedaghat2
1Department of Mechanical Engineering, Khomeinishahr Branch, Islamic Azad University, Khomeinishahr, Isfahan, Iran
2Department of Mechanical Engineering, Isfahan University of Technology, Isfahan, Iran

Tóm tắt

Liquid desiccant air conditioning system with natural convection was presented previously as a new generation of AC systems. The system consists of two three-fluid energy exchangers namely absorber and regenerator in which the action of air dehumidifying and desiccant regeneration is done, respectively. The influence of working parameters on system performance including the heat source and heat sink temperature, concentration of desiccant solution fills the system initially and humidity content of inlet air to regenerator is investigated experimentally. The heat source temperatures of 50 °C and 60 °C, heat sink temperatures of 15 °C and 20 °C and desiccant concentrations of 30% and 34%, are examined here. The inlet air to regenerator has temperature of 38.5 °C and three relative humidity of 14%, 38% and 44%. In all experiments, the inlet air to absorber has temperature of 31 °C and relative humidity of 75%. By inspecting evaluation indexes of system, it is revealed that higher startup desiccant concentration solution is more beneficial for all study cases. It is also observed although the highest/lowest temperature heat source/heat sink is most suitable for best system operation, increasing the heat source temperature should be accompanied with decreasing heat sink temperature. Using drier air stream for regenerator inlet does not necessarily improve system performance; and the air stream with proper value of humidity content should be employed. Finally after running the system in its best working condition, the coefficient of performance (COP) reached 4.66 which verified to be higher than when the same air conditioning task done by a conventional vapor compression system, in which case the COP was 3.38.

Tài liệu tham khảo

ASHRAE. (2008) HVAC Systems and Equipment HandbookAir-to-Air Energy Recovery, Atlanta, pp 10–16 Bergman TL, Incropera FP (2011) Fundamentals of heat and mass transfer John Wiley & Sons Erb B, Ahmadi MS, Simonson CJ, Besant RW (2009) Experimental Measurements of a Run-Around Membrane Energy Exchanger (RAMEE) with Comparison to a Numerical Model. ASHRAE Trans 115 Fan H, Simonson CJ, Besant RW, Shang W (2006) Performance of a run-around system for HVAC heat and moisture transfer applications using cross-flow plate exchangers coupled with aqueous lithium bromide. HVAC&R Research 12:313–336 Fazilati MA, Sedaghat A, Alemrajabi AA (2016) Natural induced flow due to concentration gradient in a liquid desiccant air dehumidifier. Appl Therm Eng 105:105–117 Fazilati MA, Sedaghat A, Alemrajabi A-A (2017) Transient performance and temperature field of a natural convection air dehumidifier loop. Heat Mass Transf:1–10 Fazilati MA, Alemrajabi AA, Sedaghat A (2017) Liquid desiccant air conditioning system with natural convection. Appl Therm Eng 115:305–314 Ge G, Moghaddam DG, Abdel-Salam AH, Besant RW, Simonson CJ (2014) Comparison of experimental data and a model for heat and mass transfer performance of a liquid-to-air membrane energy exchanger (LAMEE) when used for air dehumidification and salt solution regeneration. Int J Heat Mass Transf 68:119–131 Hemingson HB, Simonson CJ, Besant RW (2011) Steady-state performance of a run-around membrane energy exchanger (RAMEE) for a range of outdoor air conditions. Int J Heat Mass Transf 54:1814–1824 Isetti C, Nannei E, Magrini A (1997) On the application of a membrane air—liquid contactor for air dehumidification. Energy and Buildings 25:185–193 Jain S, Tripathi S, Das RS (2011) Experimental performance of a liquid desiccant dehumidification system under tropical climates. Energy Convers Manag 52:2461–2466 Lowenstein A (2008) Review of liquid desiccant technology for HVAC applications. Hvac&R Research 14:819–839 Mahmud K, Mahmood GI, Simonson CJ, Besant RW (2010) Performance testing of a counter-cross-flow run-around membrane energy exchanger (RAMEE) system for HVAC applications. Energ. Buildings 42:1139–1147 Ren CQ (2008) Effectiveness–NTU relation for packed bed liquid desiccant–air contact systems with a double film model for heat and mass transfer. Int J Heat Mass Transf 51:1793–1803 Seyed-Ahmadi M, Erb B, Simonson CJ, Besant RW (2009) Transient behavior of run-around heat and moisture exchanger system. Part І: Model formulation and verification. Int. J. Heat Mass Transf. 52:6000–6011 Simonson C, Besant R (1999) Energy wheel effectiveness: part I—development of dimensionless groups. Int J Heat Mass Transf 42:2161–2170 Vali A, Simonson CJ, Besant RW, Mahmood G (2009) Numerical model and effectiveness correlations for a run-around heat recovery system with combined counter and cross flow exchangers. Int J Heat Mass Transf 52:5827–5840 World energy outlook 2012 (2012): executive summary International energy agency (IEA) Zhang L-Z (2010) An analytical solution for heat mass transfer in a hollow fiber membrane based air-to-air heat mass exchanger. J Membr Sci 360:217–225 Zhang L, Zhu D, Deng X, Hua B (2005) Thermodynamic modeling of a novel air dehumidification system. Energ. Buildings 37:279–286 Zhang L-Z, Huang S-M, Pei L-X (2012) Conjugate heat and mass transfer in a cross-flow hollow fiber membrane contactor for liquid desiccant air dehumidification. Int J Heat Mass Transf 55:8061–8072 Zhang L-Z, Huang S-M, Chi J-H, Pei L-X (2012) Conjugate heat and mass transfer in a hollow fiber membrane module for liquid desiccant air dehumidification: a free surface model approach. Int J Heat Mass Transf 55:3789–3799