Experimental results of a supplementary technique for auto-reclosing EHV/UHV transmission lines

IEEE Transactions on Power Delivery - Tập 17 Số 3 - Trang 702-707 - 2002
M.M. Eissa1, O.P. Malik2
1MIEEE, Department of Electrical Engineering, Helwan University, Cairo, Egypt
2FIEEE, Department of Electrical Engineering, University of Calgary, Calgary, AB, Canada

Tóm tắt

A technique to discriminate between the line charging inrush current and the current resulting on closing or auto-reclosing a faulted EHV/UHV transmission line has been implemented on a 32-b digital signal processor (DSP) board. The technique is based on the voltage signals before switching and the current signals. This technique is proposed to be a supplement to the main protection schemes for both single-circuit and double-circuit lines. The scheme is tested on a physical model of a transmission system with a source at each end. Laboratory tests show that the proposed technique is effective for three-pole and single-pole reclosing on a faulted or healthy line.

Từ khóa

#Transmission lines #Voltage #Circuit faults #Protection #Relays #Laboratories #Testing #Protective relaying #Fault currents #Surges

Tài liệu tham khảo

10.1109/61.400862 10.1109/61.754073 10.1109/61.660861 10.1109/61.772315 10.1109/61.544250 10.1109/61.517482 1998, Technical Reference Manual 10.1109/61.108900 10.1109/61.736700 10.1109/61.636904 10.1109/TPAS.1985.319161 10.1109/TPWRD.1987.4308218 10.1109/61.35628 10.1109/61.660907 10.1109/61.19200 10.1109/TPWRD.1986.4307930